Search results for " IEEE Standard 1459-2000"

showing 1 items of 1 documents

A time domain strategy for the measurement of IEEE Standard 1459-2000 power quantities in nonsinusoidal three-phase and single-phase systems

2008

This paper describes a time domain technique for the detection of fundamental and harmonic components of voltages and currents, which is able to evaluate all the quantities required by IEEE standard 1459-2000. The technique does not require any spectral analysis to separate the fundamental positive-sequence components from harmonic, negative-sequence and zero-sequence ones. In the paper the development of the proposed technique is presented for three-phase systems, both three-wires and four-wires, as well as for single-phase systems. The implementation of the proposed technique on a PC-based instrument is also described and experimental results are presented. Finally, accuracy specification…

Total harmonic distortionEngineeringbusiness.industryEnergy Engineering and Power TechnologyHarmonic distortion IEEE Standard 1459-2000 phase-locked loops (PLLs) power measurement power quality.Power (physics)Harmonic analysisPhase-locked loopThree-phasePersonal computerHarmonicElectronic engineeringTime domainElectrical and Electronic EngineeringbusinessSettore ING-INF/07 - Misure Elettriche E Elettroniche
researchProduct